North America Icon North America
Latin America Icon Latin America

Product Catalogue

You are in: Home | Catalogue | AFIREFENIX MICA RZ1-K & SZ1-K 0,6/1 kV PH120 (AS+)
Back to product search

AFIREFENIX MICA RZ1-K & SZ1-K 0,6/1 kV PH120 (AS+)

Standards

UNE 211025
(Construction & tests)

EN 50200, EN IEC 60331-1, IEC 60331-1 & 2
(Fire resistance PH120)

CPR Regulation (EU) No 305/2011:
Reaction to fire (Cca-s1b, d1, a1)

LOW VOLTAGE DIRECTIVE: 2014/35/EU

RoHS compliant.

Quality certificate

Certificate icon AENOR certificationCertificate icon Low voltage Directive (LVD): 2014/35/EUCertificate icon CPR compliantCertificate icon CE markingCertificate icon RoHS

Technical characteristics & performances

  • Single-core Propiedad del cable: Single-core
  • Multicore Propiedad del cable: Multicore
  • Flexible Propiedad del cable: Flexible
  • Bunched conductor (class 5) mm2 Propiedad del cable: Bunched conductor (class 5) mm2
  • Maximum service temperature: 90ºC / 250ºC Propiedad del cable: Maximum service temperature: 90ºC / 250ºC
  • 0,6/1 (1,2) kV C.A / 1,5 (1,8) kV C.C Propiedad del cable: 0,6/1 (1,2) kV C.A / 1,5 (1,8)  kV C.C
  • Easy peeling / easy strip Propiedad del cable: Easy peeling / easy strip
  • Easy installation Propiedad del cable: Easy installation

Fire performance

  • Fire resistance Propiedad del cable: Fire resistance
  • Cca-s1b,d1,a1 (reaction to fire) Propiedad del cable: Cca-s1b,d1,a1 (reaction to fire)
  • Flame retardant Propiedad del cable: Flame retardant
  • Fire retardant Propiedad del cable: Fire retardant
  • Low heat emission Propiedad del cable: Low heat emission
  • Low production of flaming droplets Propiedad del cable: Low production of flaming droplets
  • Low opacity & production of smoke Propiedad del cable: Low opacity & production of smoke
  • Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm Propiedad del cable: Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm

Uses and applications

  • Installations with risk of fire or explosion Propiedad del cable: Installations with risk of fire or explosion
  • BD2, BD3, BD4 (skyscrapers, tunnels…) Propiedad del cable: BD2, BD3, BD4 (skyscrapers, tunnels…)
  • Safety installations in case of fire Propiedad del cable: Safety installations in case of fire
  • Buildings receiving the public Propiedad del cable: Buildings receiving the public

Packaging

  • Coil Propiedad del cable: Coil
  • Drum Propiedad del cable: Drum


Functional features

  • Technical designation:
    SZ1-K 0.6/1 kV PH120 (AS+)   (S≤10 mm2).
    MICA RZ1-K 0.6/1 kV PH120 (AS+)  (S≥16 mm2).
  • Constructive description:
    Standards (structure/tests): UNE 211025.

    Construction structure:
    SZ1-K 0.6/1 kV PH120 (AS+)   (S≤10 mm2).
    Conductor: Copper, class 5 acc. to EN 60228, IEC 60228.
    Insulation: Silicone
    Oversheath: Thermoplastic polyolefin HFFR type ST8 acc. to IEC 60502-1.

    MICA RZ1-K 0.6/1 kV PH120 (AS+)  (S≥16 mm2)
    Conductor: Copper, class 5 acc. to EN 60228, IEC 60228.
    Insulation: Mica + XLPE tape
    Oversheath: Thermoplastic polyolefin HFFR type ST8 acc. to IEC 60502-1.

    • Rated voltage (Uo/U): 0.6/1 kV AC.

    • Max. conductor temperature. Normal operation / short-circuit (t≤5s): 90 / 250ºC.

    • Range: Single-core or multicore cable.
    Configurations: 1x(1.5-...-500) mm2 / 2x(1.5-...-50) mm2 / (3-4)x o G(1.5-...-120) mm2 / 5G(1.5-...-95) mm2.

    • Identification: Sheath colour: Orange.
    — Multicore cables (From 2 to 5): HD 308 S2 (2x 3x 3G 4x 4G 5G).

    • Presentation and packaging: Drum/cut to length (Miguélez code = 03) and  coils (100 m - Miguélez code = 00) .
  • Rated voltage:
    0.6/1 kV
  • Normal operation temperature:
    90 ºC
  • Short-circuit temperature (5 s max):
    250 ºC (t<5s)
  • Voltage test:
    3,5 kV C.A.
  • Colour:
    Oversheath (Orange) / Insulations (HD 308 S2).
  • Fire performance:
    Fire resistance: PH120 (EN 50200, EN IEC 60331-1, IEC 60331-1 & 2).

    Reaction to fire (CPR - EN 50575 & EN 13501-6): class Cca-s1b,d1,a1.

    Additional performance in case of fire (if the Construction Products Regulation is not applicable):
    Flame retardant, fire retardant, halogen-free and low gas and smoke emission with low opacity/toxicity/corrosivity/conductivity
    (IEC 60332-1-2, IEC 60332-3-24, IEC 60754-1, IEC 60754-2, IEC 61034-2).
  • Type of installation:
    Fixed
  • User´s guide:
    Fixed installation. Especially designed for use as a power, control or command cable in installations
    where the power supply of certain circuits must be preserved regardless of being directly affected by fire.

    Specifically intended for non-autonomous safety circuits or circuits with centralised autonomous power systems, alarm circuits, signalling and emergency lighting, acoustic warning, exhaust fans and water pumps for fire suppression.
  • Technical instructions:
    .
  • Conductor:
    Flexible
  • Halogen free:
    Yes
  • Armoured cable:
    No

SEARCH CPR

Search DoP

or search in

PUBLICATIONS DoP