Standards
UNE 211025
(Construction & tests)
EN 50200, EN IEC 60331-1, IEC 60331-1 & 2
(Fire resistance PH120)
CPR Regulation (EU) No 305/2011:
Reaction to fire (Cca-s1b, d1, a1)
LOW VOLTAGE DIRECTIVE: 2014/35/EU
RoHS compliant.
Quality certificate
Technical characteristics & performances
- Single-core
- Multicore
- Flexible
- Bunched conductor (class 5) mm2
- Maximum service temperature: 90ºC / 250ºC
- 0,6/1 (1,2) kV C.A / 1,5 (1,8) kV C.C
- Easy peeling / easy strip
- Easy installation
Fire performance
- Fire resistance
- Cca-s1b,d1,a1 (reaction to fire)
- Flame retardant
- Fire retardant
- Low heat emission
- Low production of flaming droplets
- Low opacity & production of smoke
- Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
Uses and applications
- Installations with risk of fire or explosion
- BD2, BD3, BD4 (skyscrapers, tunnels…)
- Safety installations in case of fire
- Buildings receiving the public
Packaging
- Coil
- Drum
Functional features
-
Technical designation:
SZ1-K 0.6/1 kV PH120 (AS+) (S≤10 mm2).
MICA RZ1-K 0.6/1 kV PH120 (AS+) (S≥16 mm2). -
Constructive description:
Standards (structure/tests): UNE 211025.
Construction structure:
SZ1-K 0.6/1 kV PH120 (AS+) (S≤10 mm2).
Conductor: Copper, class 5 acc. to EN 60228, IEC 60228.
Insulation: Silicone
Oversheath: Thermoplastic polyolefin HFFR type ST8 acc. to IEC 60502-1.
MICA RZ1-K 0.6/1 kV PH120 (AS+) (S≥16 mm2)
Conductor: Copper, class 5 acc. to EN 60228, IEC 60228.
Insulation: Mica + XLPE tape
Oversheath: Thermoplastic polyolefin HFFR type ST8 acc. to IEC 60502-1.
• Rated voltage (Uo/U): 0.6/1 kV AC.
• Max. conductor temperature. Normal operation / short-circuit (t≤5s): 90 / 250ºC.
• Range: Single-core or multicore cable.
Configurations: 1x(1.5-...-500) mm2 / 2x(1.5-...-50) mm2 / (3-4)x o G(1.5-...-120) mm2 / 5G(1.5-...-95) mm2.
• Identification: Sheath colour: Orange.
— Multicore cables (From 2 to 5): HD 308 S2 (2x 3x 3G 4x 4G 5G).
• Presentation and packaging: Drum/cut to length (Miguélez code = 03) and coils (100 m - Miguélez code = 00) . -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
90 ºC
-
Short-circuit temperature (5 s max):
250 ºC (t<5s)
-
Voltage test:
3,5 kV C.A.
-
Colour:
Oversheath (Orange) / Insulations (HD 308 S2).
-
Fire performance:
• Fire resistance: PH120 (EN 50200, EN IEC 60331-1, IEC 60331-1 & 2).
• Reaction to fire (CPR - EN 50575 & EN 13501-6): class Cca-s1b,d1,a1.
• Additional performance in case of fire (if the Construction Products Regulation is not applicable):
Flame retardant, fire retardant, halogen-free and low gas and smoke emission with low opacity/toxicity/corrosivity/conductivity
(IEC 60332-1-2, IEC 60332-3-24, IEC 60754-1, IEC 60754-2, IEC 61034-2). -
Type of installation:
Fixed
-
User´s guide:
Fixed installation. Especially designed for use as a power, control or command cable in installations
where the power supply of certain circuits must be preserved regardless of being directly affected by fire.
Specifically intended for non-autonomous safety circuits or circuits with centralised autonomous power systems, alarm circuits, signalling and emergency lighting, acoustic warning, exhaust fans and water pumps for fire suppression. -
Technical instructions:
.
-
Conductor:
Flexible
-
Halogen free:
Yes
-
Armoured cable:
No