AFIREFENIX SHIELD SOZ1-K (AS+) 300/500V PH120

Standards

UNE 211025 (Construction and tests)

Low Voltage Directive: 2014/35/UE

CPR Regulation Nº 305/2011/UE:
Reaction to fire (Cca-s1b,d1,a1)

Additional performance in case of fire (if the CPR is not applicable):
IEC 60332-1-2, IEC 60332-3-24, IEC 60754-1 & 2 e IEC 61034-2.

Fire resistance: PH120
EN 50200 & IEC 60331-2

RoHS compliant.

Quality certificate

Certificate icon Low voltage Directive (LVD): 2014/35/EUCertificate icon CPR compliantCertificate icon CE markingCertificate icon RoHS

Technical characteristics & performances

  • Multicore Propiedad del cable: Multicore
  • Bunched conductor (class 5) mm2 Propiedad del cable: Bunched conductor (class 5) mm2
  • Maximum service temperature: 90ºC / 250ºC Propiedad del cable: Maximum service temperature: 90ºC / 250ºC
  • 300 / 500 V C.A. Propiedad del cable: 300 / 500 V C.A.
  • Easier pulling Propiedad del cable: Easier pulling
  • Easy peeling / easy strip Propiedad del cable: Easy peeling / easy strip
  • Easy installation Propiedad del cable: Easy installation
  • Protection against Electromagnetic disturbances Propiedad del cable: Protection against Electromagnetic disturbances

Fire performance

  • Fire resistance Propiedad del cable: Fire resistance
  • Cca-s1b,d1,a1 (reaction to fire) Propiedad del cable: Cca-s1b,d1,a1 (reaction to fire)
  • Fire retardant Propiedad del cable: Fire retardant
  • Low heat emission Propiedad del cable: Low heat emission
  • Low production of flaming droplets Propiedad del cable: Low production of flaming droplets
  • Low opacity & production of smoke Propiedad del cable: Low opacity & production of smoke
  • Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm Propiedad del cable: Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
  • Halogen free Propiedad del cable: Halogen free
  • Low emission of toxic gases Propiedad del cable: Low emission of toxic gases

Uses and applications

  • Safety installations in case of fire Propiedad del cable: Safety installations in case of fire
  • Buildings receiving the public Propiedad del cable: Buildings receiving the public
  • Industral use Propiedad del cable: Industral use
  • Indoor use Propiedad del cable: Indoor use

Packaging

  • Coil Propiedad del cable: Coil
  • Drum Propiedad del cable: Drum


Functional features

  • Technical designation:
    SOZ1-K (AS+) 300/500 V PH120
  • Constructive description:
    Shielded multicore cable with intrinsic resistance to fire (AS+), halogen free.

    CONSTRUCTION:
    Conductor: Annealed copper, class 5 acc. to IEC 60228.
    Insulation: Silicone. 
    Core identification: 2x - red and black.
    Shield: Al/PET tape with a drain wire of tinned copper.
    Shield coverage (100 %).
    Oversheath: Thermoplastic polyolefin, LSZH. Color: red (or orange on request and MOQ).

    Range: Multicore cable. Configurations: 2x1,5 mm2 & 2x2,5 mm2.
  • Rated voltage:
    300/500 V
  • Normal operation temperature:
    90 ºC
  • Short-circuit temperature (5 s max):
    250 ºC (t<5s)
  • Voltage test:
    2 kV (15 min)
  • Colour:
    Oversheath (red) / Core identification: 2x - red & black cores.
  • Fire performance:
    Fire resistance: PH120 (EN 50200, IEC 60331-2)

    Reaction to fire (CPR - EN 50575 & EN 13501-6): Cca-s1b,d1,a1.

    Additional performance in case of fire (if the Construction Products Regulation is not applicable):
    Fire resistant, fire & flame retardant, halogen-free and low gas and smoke emission with low opacity/toxicity/corrosivity/conductivity
    (IEC 60332-1-2, IEC 60332-3-24, IEC 61034-2, IEC 60754-1 e IEC 60754-2).
  • Type of installation:
    Fixed
  • User´s guide:
    Shielded cable with intrinsic resistance to fire, recommended for electrical circuits that require protection against disturbances and electromagnetic interference.
    Specifically designed for use in security circuits associated with fire-fighting equipment, signaling, detection and alarm systems (pushbuttons, detectors...).

    — Ambient operating temperature (ranges):
    • Minimum: - 30 ºC (static – without exposure to movement, mechanical damages, shocks, or vibrations).
    • Maximum: + 70 ºC.
    • Minimum temperature for cable laying during installation and assembly of accessories: 0 ºC. 

    — Minimum bending radius: 10 x D. D = overall diameter of the cable in mm.

    — Maximum pulling force:
    • If the traction force is applied on the copper conductors: F = 50xS (N). "S" = cross sectional area of conductors (mm2).
    • If the traction force is applied on the oversheath: F = 3xD2 (N). "D" = overall diameter of the cable (mm).
  • Technical instructions:
    .
  • Conductor:
    Flexible
  • Halogen free:
    Yes
  • Armoured cable:
    No