Standards
EN 50525-3-31 & UNE 211002
(Construction & tests)
Low voltage Directive: 2014/35/UE
CPR REGULATION 305/2011/UE:
Reaction to fire (B2ca - s1a, d1, a1)
TYPE2: IEC 60332-3-24; EN 60332-3-24
Fire retardant
RoHS compliant
Quality certificate
Technical characteristics & performances
- Single-core
- Bunched conductor (class 5) mm2
- Maximum service temperature: 70ºC / 160ºC
- 450 / 750 V C.A.
- Easier pulling
- Easy peeling / easy strip
Fire performance
- B2ca-s1a,d1,a1 (reaction to fire)
- Flame retardant
- Fire retardant
- Low heat emission
- Low production of flaming droplets
- Low opacity & production of smoke
- Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
- Halogen free
- Low emission of toxic gases
Uses and applications
- Panel and appliance wiring
- Installations with risk of fire or explosion
- BD2, BD3, BD4 (skyscrapers, tunnels…)
- Buildings receiving the public
- Residential use
Packaging
- Coil
- Reel
- Drum
Functional features
-
Technical designation:
H07Z1-K(AS)TYPE 2
-
Constructive description:
EN 50525-3-31 & UNE 211002 (Construction and tests)
Single core non-sheathed cables with halogen-free thermoplastic insulation, and low emission of smoke
- CONDUCTOR:
Flexible, annealed, plain copper conductor, class 5 acc. to IEC 60228, EN 60228.
- INSULATION:
Halogen free insulation of thermoplastic polyolefin compound, type TI7 acc.to EN 50363-7.
Number of cores: 1
Cross-sectional area size range: From 1,5 to 240 mm2. -
Rated voltage:
450/750 V
-
Normal operation temperature:
70ºC
-
Short-circuit temperature (5 s max):
160ºC
-
Voltage test:
2,5 kV AC
-
Colour:
INSULATION: black, brown, gray, blue, yellow-green, red, white. Other colours on request.
-
Fire performance:
REACTION TO FIRE. StandardsDeclared performances: B2ca-s1a, d1, a1 (EN 50575:2014+A1:2016)- Flame retardant: EN 60332-1-2; IEC 60332-1 (H≤425 mm)- Fire retardant: EN 50399 (Fs ≤ 1,5 m - Flame source: 20,5 kW)- Heat generation: EN 50399 (20,5 kW) (THR ≤ 15 MJ & Peak HRR ≤ 30 kW; FIGRA ≤ 150 W/s)- Low production and opacity of emitted smokes:s1 (EN 50399): TSP ≤ 50 m2 & Peak SPR ≤ 0,25 m2/ss1a: “s1” & transmittance > 80 % (EN 61034-2; IEC 61034- 2)- Flaming droplets and/or particles: EN 50399 (llama: 20,5 kW):d1: If no flaming droplets/particles persisting longer than 10 s occurs within 1200 seconds- Low acidity and conductivity of the emitted gases: EN 60754-2; IEC 60754-2:a1: acidity(pH≥4,3) & conductivity < 2,5 microSiemens/mm- System AVCP: 1+- Notified body: 0099 AENOR S.A.U.- DoP: MB2H07Z1KTYPE2For covered range (+ information), please check out "CPR/DoP" section in our website.
*The packaging labels of these cables include the CE marking according to the CPR Regulation ((EU) Nº 305/2011) articles 8 and 9Other performances:
- Fire retardant: EN 60332-3-24 / IEC 60332-3-24 (cat.C)
- Halogen free. Low emission of toxic gases: EN 60754-1 / IEC 60754-1 -
Type of installation:
Fixed
-
User´s guide:
It is specially indicated for its use in public concurrence places (airports, museums, malls, schools, hospitals, cinemas,...) and, in general, whenever an important fire risk exists or where it´s required a low level of smoke and corrosive gazes emmisions in case of fire or burning.
Its special fire performance protects public health, fireman works and avoid any possible damage to electronic equipments.
TYPE 2 cables are for use where special fire performance is necessary, or where local conditions or regulations require increased leves of public safety. They are especially suitable where cables are installed in bunches.
Installation in surface-mounted or embedded conduits, or similar closed systems (tube, conduit, cable ducting or similar closed systems). It is suitable for fixed installations with complex paths where its flexibility allows an easier installation.
They are recommended for fixed and protected installation in lighting and control gear for voltages up to and including 1.000 V A.C or up to 750 D.C to earth. -
Conductor:
Flexible
-
Halogen free:
Yes
-
Armoured cable:
No