Standards
IEC 60502-1, UNE 21123-4
(Construction and tests)
LOW VOLTAGE DIRECTIVE: 2014/35 / EU
Regulation CPR (EU) No 305/2011:
Reaction to fire (Cca-s1b, d1, a1)
RoHS compliant
Quality certificate





Technical characteristics & performances
-
Multicore
-
Bunched conductor (class 5) mm2
-
Maximum service temperature: 90ºC / 250ºC
-
0,6/1 (1,2) kV C.A
-
Oil resistance
-
Low temperature resistance
Fire performance
-
Cca-s1b,d1,a1 (reaction to fire)
-
Flame retardant
-
Fire retardant
-
Low heat emission
-
Low production of flaming droplets
-
Low opacity & production of smoke
-
Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
-
Halogen free
-
Low emission of toxic gases
Uses and applications
-
Panel and appliance wiring
-
Control & command
-
Installations with risk of fire or explosion
-
BD2, BD3, BD4 (skyscrapers, tunnels…)
-
Buildings receiving the public
-
Industral use
-
Outdoor use
Packaging
-
Drum
Functional features
-
Technical designation:
RZ1-K (AS) 0,6/1 kV
-
Constructive description:
IEC 60502-1, UNE 21123-4 (Construction and tests)
- CONDUCTOR:
Flexible, annealed, plain copper conductor, class 5 based on standard IEC 60228 .
- INSULATION:
Cross-linked polyethylene (XLPE) according to International standard IEC 60502-1
- ASSEMBLY OF CONDUCTORS:
The cores are cabled helically.
- FILLER:
Extruded. Optional for multicore cables. Halogen free thermoplastic material, suitable for the operating temperature of the cable and compatible with the insulating and sheathing material.
- OVERSHEATH:
Extruded polyolefin type ST8 according to International standard IEC 60502-1.
Core identification is according to standard EN 50334.
All cores in the cable are black and have an inscription along the whole length of them, except one core
which is coloured green/yellow (this core isn´t numbered).
The inscription is composed of marks repeated at regular intervals along the whole length of the core.
Each mark comprises:
- A reference number beginning at 1 in Arabic numerals;
- A dash which underlines this number and indicates the direction in which the number should be read. -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
90ºC
-
Short-circuit temperature (5 s max):
250ºC
-
Voltage test:
3,5 kV (5 minutes)
-
Colour:
Sheath: Green / Insulation: According to HD 308 S2, UNE 21089-1
-
Fire performance:
- Reaction to fire: Cca-s1b, d1, a1 (EN 50575:2014+A1:2016)
• EN 60332-1-2; IEC 60332-1 (H≤425 mm) Flame retardant
• EN 50399 (flame source: 20,5 kW) Fs ≤ 2 m Fire retardant
• Low heat generation: EN 50399 (flame source: 20,5 kW)
- Total heat released: THR ≤ 30 MJ
- Maximum value of the heat released: Peak HRR ≤ 60 kW
- Indication of heat increase: FIGRA ≤ 300 W/s
• Low production and opacity of emitted smokes:
- s1 (EN 50399):
-Total smoke production: (TSP) ≤ 50 m2
-Maximum value of smokes released : (Peak SPR) ≤ 0,25 m2/s
- s1b: s1 and 60% < Transmittance < 80 % (UNE EN 61034-2; IEC 61034-2)
• Low production of flaming droplets (EN 50399 - flame source:20,5 kW):
- d1: No flaming droplets/particles persisting longer than 10' occurs within 1200'.
• Low acidity and conductivity of the emitted gases:
- a1: pH≥4,3 conductivity < 2,5 ?S/mm (EN 60754-2; IEC 60754-2)
For covered range (+ information), please check out "CPR/DoP" section in our website.
*The packaging labels of these cables include the CE marking according to the CPR Regulation ((UE) Nº 305/2011) articles 8 and 9.
Other performances:
- Fire retardant: UNE EN 60332-3-24 / IEC 60332-3-24 (cat.C)
- Halogen free. Low emission of toxic gases: UNE EN 50267-2-1 / IEC 60754-1 -
Type of installation:
Fixed
-
User´s guide:
It is specially indicated as a control cable in distribution networks, public concurrence places (airports, underground, museums, malls, schools, hospitals, cinemas, tunnels ...) and in general, whenever an important fire risk exists or where it´s required a low smoke emission and corrosive gases in case of fire.
Its special fire performance protects public health, fireman works and avoid any possible damage to electronic equipments.
It is suitable for fixed installations with complex paths where its flexibility allows an easier installation.
“ (...)For electrical energy transport and distribution, distribution networks, protected or not. For indoor and outdoor installations. Non suitable for facilities of feeding of submerged pumps. (...)” (UNE21123-4). -
Conductor:
Flexible
-
Halogen free:
Yes
-
Armoured cable:
No