Standards
IEC 60502-1 (Construction and tests)
LOW VOLTAGE DIRECTIVE: 2014/35 / EU
CPR Regulation (EU) No 305/2011:
Reaction to fire (Eca)
Other fire performances (when CPR Regulation is not applicable): IEC 60332-1-2, IEC 60332-3-24, IEC 60754-1, IEC 60754-2 & IEC 61034-2.
RoHS compliant
Quality certificate
Technical characteristics & performances
- Single-core
- Multicore
- Bunched conductor (class 5) mm2
- Maximum service temperature: 90ºC / 250ºC
- 0,6/1 (1,2) kV C.A
- Low temperature resistance
- Easy peeling / easy strip
- Protection against Electromagnetic disturbances
Fire performance
- Eca (reaction to fire)
- Flame retardant
- Fire retardant
- Low opacity & production of smoke
- Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
- Halogen free
- Low emission of toxic gases
Uses and applications
- Control & command
- Distribution networks
- Industral use
- Outdoor use
Packaging
- Drum
DOWNLOADS:
Technical DatasheetFunctional features
-
Technical designation:
RC4Z1-K 0,6/1 kV
-
Constructive description:
IEC 60502-1 (Construction and tests)
- CONDUCTOR:
Flexible, annealed, plain copper conductor, class 5 based on International standard IEC 60228.
- INSULATION:
Cross-linked polyethylene (XLPE) according to International standard IEC 60502-1
- ASSEMBLY OF CONDUCTORS:
In multicore cables, the cores are cabled helically.
- SHIELD:
Al/PET tape + tinned copper braid with a coverage greater than 65%.
NOTE: Other particular shields on request.
- OVERSHEATH:
HFFR type ST8 according to International standard IEC 60502-1.
Identification of cores HD 308 S2:
2x - brown and blue
3x - brown, black and gray
3G - brown, blue and yellow / green
4x - brown, black, gray, blue
4G - brown, black, gray, yellow / green
5G - brown, black, gray, blue, yellow / green
Identification of cores (n>5): EN 50334.
Black numbered cores + G/Y core. -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
90ºC
-
Short-circuit temperature (5 s max):
250ºC
-
Voltage test:
3,5 kV
-
Colour:
Oversheath: Green or black / Insulation: -Multicore cable from 2 up to 5 (HD 308 S2); -Multicore cable n>5 (EN 50334)
-
Fire performance:
- Reaction to fire: Eca (EN 50575:2014+A1:2016)
• EN 60332-1-2; IEC 60332-1 (H≤425 mm) Flame retardant
For covered range (+ information), please check out "CPR/DoP" section in our website.
*The packaging labels of these cables include the CE marking according to the CPR Regulation ((EU) Nº 305/2011) articles 8 and 9.
Other fire performances (when CPR Regulation is not applicable):
- Flame retardant: EN 60332-1-2, IEC 60332-1-2.
- Fire retardant: UNE-EN 60332-3-24 / IEC 60332-3-24 (cat. C).
- Halogen free. Low emission of toxic gases: EN 60754-1 / IEC 60754-1 (HCl < 0,5 %).
- Low opacity of emitted smokes: EN 61034-2; IEC 61034-2 (Transmittance > 60 %).
- Low acidity and conductivity of the emitted gases: EN 60754-2; IEC 60754-2 (pH≥4,3 & conductivity < 2,5 microS/mm). -
Type of installation:
Fixed
-
User´s guide:
Afirenas SHIELD RC4Z1-K 0,6/1 kV power, control & command cables are specially indicated for its use in distribution networks, power stations, industries or buildings and electrical installations where we need a protection against electromagnetic interference (EMC).
-
Technical instructions:
.
-
Conductor:
Flexible
-
Halogen free:
Yes
-
Armoured cable:
No