You are in: Home | Catalogue | AFIRENAS X-B2 RZ1-K (AS) 0,6/1 kV
Back to product search

AFIRENAS X-B2 RZ1-K(AS) 0,6/1 kV

Standards

IEC 60502-1 & UNE 21123-4
(Construction and tests)

LOW VOLTAGE DIRECTIVE: 2014/35 / EU

CPR Regulation (EU) No 305/2011:
Reaction to fire
(B2ca-s1a,d1,a1 (1x)
B2ca-s1b,d1,a1 (2x/3x/3G/4x/4G/5G).)

RoHS compliant

Quality certificate

Certificate icon AENOR certificationCertificate icon CESMEC certificationCertificate icon CPR compliantCertificate icon CE markingCertificate icon RoHS

Technical characteristics & performances

  • Single-core Propiedad del cable: Single-core
  • Multicore Propiedad del cable: Multicore
  • Bunched conductor (class 5) mm2 Propiedad del cable: Bunched conductor (class 5) mm2
  • Maximum service temperature: 90ºC / 250ºC Propiedad del cable: Maximum service temperature: 90ºC / 250ºC
  • 0,6/1 (1,2) kV C.A / 1,5 (1,8) kV C.C Propiedad del cable: 0,6/1 (1,2) kV C.A / 1,5 (1,8)  kV C.C
  • Low temperature resistance Propiedad del cable: Low temperature resistance
  • Easier pulling Propiedad del cable: Easier pulling
  • Easy peeling / easy strip Propiedad del cable: Easy peeling / easy strip

Fire performance

  • B2ca-s1b,d1,a1 (reaction to fire) Propiedad del cable: B2ca-s1b,d1,a1 (reaction to fire)
  • B2ca-s1a,d1,a1 (reaction to fire) Propiedad del cable: B2ca-s1a,d1,a1 (reaction to fire)
  • Flame retardant Propiedad del cable: Flame retardant
  • Fire retardant Propiedad del cable: Fire retardant
  • Low heat emission Propiedad del cable: Low heat emission
  • Low production of flaming droplets Propiedad del cable: Low production of flaming droplets
  • Low opacity & production of smoke Propiedad del cable: Low opacity & production of smoke
  • Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm Propiedad del cable: Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
  • Halogen free Propiedad del cable: Halogen free
  • Low emission of toxic gases Propiedad del cable: Low emission of toxic gases

Uses and applications

  • Installations with risk of fire or explosion Propiedad del cable: Installations with risk of fire or explosion
  • BD2, BD3, BD4 (skyscrapers, tunnels…) Propiedad del cable: BD2, BD3, BD4 (skyscrapers, tunnels…)
  • Buildings receiving the public Propiedad del cable: Buildings receiving the public
  • Residential use Propiedad del cable: Residential use
  • Industral use Propiedad del cable: Industral use
  • Exterior lighting Propiedad del cable: Exterior lighting
  • Outdoor use Propiedad del cable: Outdoor use
  • Indoor use Propiedad del cable: Indoor use

Packaging

  • Drum Propiedad del cable: Drum


Functional features

  • Technical designation:
    RZ1-K(AS) 0,6/1 kV
  • Constructive description:
    IEC 60502-1, UNE 21123-4 (Construction and tests).

    - CONDUCTOR: Flexible, annealed, plain copper conductor, class 5 acc. to IEC 60228.
    - INSULATION: Cross-linked polyethylene (XLPE) acc. to IEC 60502-1 (type DIX 3 HD 603-1).
    - ASSEMBLY OF CONDUCTORS: In multicore cables, the cores are cabled helically.
    - FILLER: Optional for multicore cables (extruded). Halogen free thermoplastic material, suitable for the operating temperature of the cable and compatible with the insulating and sheathing material.
    - OVERSHEATH: Thermoplastic polyolefin type ST8 acc. to IEC 60502-1.

    Core identification: acc. to HD 308 S2.
    2x - brown and blue
    3x - brown, black and gray
    3G - brown, blue and yellow / green
    4x - brown, black, gray and blue
    4G - brown, black, gray and yellow / green
    5G - brown, black, gray, blue and yellow / green
  • Rated voltage:
    0.6/1 kV
  • Normal operation temperature:
    90 ºC
  • Short-circuit temperature (5 s max):
    250 ºC (t<5s)
  • Voltage test:
    3,5 kV AC (5 min.)
  • Colour:
    Oversheath colour: Green (93) / Insulation (multicore): According to HD 308 S2 & UNE 21089-1
  • Fire performance:
    Reaction to fire classification (CPR - EN 50575 & EN 13501-6):
    B2ca-s1a,d1,a1 (1x) & B2ca-s1b,d1,a1 (2x/3x/3G/4x/4G/5G).

    Other fire performance features (when CPR Regulation is not applicable):
    Flame retardant, fire retardant, halogen-free and low gas and smoke emission with low opacity/toxicity/corrosivity/conductivity
    (IEC 60332-1-2, IEC 60332-3-24, IEC 60754-1, IEC 60754-2 and IEC 61034-2).
  • Type of installation:
    Fixed
  • User´s guide:
    Especially suitable as a power, command or control cable for fixed installations in tunnels and railway infrastructures, public access premises (hospitals, airports, schools...), places with fire or explosion hazard, high-rise buildings and whenever its special fire performance behaviour is required.

    Suitable for indoor and outdoor (protected from direct and continuous exposure to UV radiation) installations on supports in the air, in conduits or directly buried.

    — Temperature ranges:
    • Maximum continuous conductor operating temperature: +90 ºC.
    • Maximum continuous conductor short-circuit temperature (t≤5s) : +250 ºC.
    • Maximum ambient temperature: +70 ºC (higher temperatures limits current-carrying capacities).
    • Minimum ambient temperature: -30 ºC (static, permanently installed, protected against mechanical damage, without exposure to movement, mechanical damages, shocks, or vibrations).
    • Minimum temperature for cable laying during installation and assembly of accessories: 0 ºC. Under normal conditions of care. This temperature is valid for the cable itself and not for the environment. If possible, the temperature of the cable shall be raised before laying, e.g., in a heated building, to facilitate handling and reduce the risk of damages.

    — Minimum bending radius: 4xD (D<25); 5xD(25≤D≤50); 6xD(D>50). D = overall diameter of the cable in mm. Bending nearby the temperature limits should be carried out extra carefully.

    — Maximum pulling force:
    If the traction force is applied on the copper conductors: F = 50 x S (N). S = cross-sectional area of the conductors (in mm2).
    If the traction force is applied on the oversheath: F = 5 x D2 (N). D = overall diameter of the cable (in mm).
    It is assumed that the cable route is well designed for the laying procedure with well-established curves and enough cable rollers. Special attention shall be paid to the required minimum bending radius.
  • Technical instructions:
    .
  • Conductor:
    Flexible
  • Halogen free:
    Yes
  • Armoured cable:
    No