Standards
EN 50525-2-31, IEC 60227-3
(Construction and tests)
Low voltage Directive: 2014/35/UE
CPR Regulation (EU) No 305/2011:
Reaction to fire (Eca)
RoHS compliant
Quality certificate




Technical characteristics & performances
-
Single-core
-
Solid conductor (class 1) mm2
-
Stranded conductor (class 2) mm2
-
Maximum service temperature: 70ºC / 160ºC
-
450 / 750 V C.A.
-
Easier pulling
-
Easy peeling / easy strip
Fire performance
-
Eca (reaction to fire)
-
Flame retardant
Uses and applications
-
Panel and appliance wiring
-
Residential use
-
Industral use
-
Earthing & grounding
-
Indoor use
Packaging
-
Coil
-
Drum
Functional features
-
Technical designation:
H07V-U (s: 1,5/2,5/4 mm2) H07V-R (s: From 6 up to 240 mm2)
-
Constructive description:
EN 50525-2-31, IEC 60227-3 (Construction and tests)
Single core non-sheathed cables with thermoplastic PVC insulation
- CONDUCTOR:
Rigid annealed plain copper conductor, class 1 (cross sectional areas: 1,5/2,5/4 mm2 – solid (-U)) or class 2 (cross sectional area ≥ 6 mm2 – stranded (-R)) according to the International, European and Spanish standards IEC 60228; EN 60228; UNE EN 60228.
- INSULATION:
Polyvinyl chloride insulation (PVC) type TI 1 acc. to EN 50363-3.
Number of cores: 1
Cross-sectional area size range:
- H07V-U : 1,5 / 2,5 /4 mm2
- H07V-R : 6 to 240 mm2 -
Rated voltage:
450/750 V
-
Normal operation temperature:
70ºC
-
Short-circuit temperature (5 s max):
160ºC
-
Voltage test:
2,5 kV
-
Colour:
*INSULATION: black, brown, gray, blue, yellow-green, red, white. Other colours on request.
-
Fire performance:
- Reaction to fire: Eca (EN 50575:2014+A1:2016)
Flame retardant: EN 60332-1-2; IEC 60332-1 (H≤425 mm)
DoP: MEH07VU & MEH07VR
For covered range (+ information), please check out "CPR/DoP" section in our website.
*The packaging labels of these cables include the CE marking according to the CPR Regulation ((EU) Nº 305/2011) articles 8 and 9. -
Type of installation:
Fixed
-
User´s guide:
H07V-U & H07V-R: Installation in surface-mounted or embedded conduits, or similar closed systems.
They are recommended for fixed and protected installation in lighting and control gear for voltages upo to and including 1.000 V A.C or up to 750 V D.C. to earth.
(EN 50565-2)
They are suitable for internal wiring in electrical boards and fixed installations in conduits. -
Technical instructions:
.
-
Conductor:
Rigid
-
Halogen free:
No
-
Armoured cable:
No