Standards
NF C 32-321 and IEC 60502-1
(Construction and tests)
Low Voltage Directive: 2014/35 / EU
Regulation CPR (EU) No 305/2011:
Reaction to fire (Eca)
RoHS compliant
Quality certificate
Technical characteristics & performances
- Multicore
- Solid conductor (class 1) mm2
- Maximum service temperature: 90ºC / 250ºC
- 0,6/1 (1,2) kV C.A
- UV resistance
- Low temperature resistance
- Presence of water
Fire performance
- Eca (reaction to fire)
- Flame retardant
Uses and applications
- Control & command
- Industral use
- Outdoor use
Packaging
- Drum
DOWNLOADS:
Quality certificateFunctional features
-
Technical designation:
U-1000 R2V
-
Constructive description:
NF C 32-321, IEC 60502-1 (Construction and tests)
- CONDUCTOR:
Annealed copper conductor, class 1(s: 1,5/2,4 or 4 mm2) or class 2 (from 6 mm2 up to 300 mm2) based on International standard IEC 60228 / EN 60228.
- INSULATION:
Cross-linked polyethylene (XLPE) according to International standard IEC 60502-1
- ASSEMBLY OF CONDUCTORS:
The cores are cabled helically.
- FILLER:
Optional. No-hygroscopic material, suitable for the operating temperature of the cable and compatible with the insulating and sheathing material.
- OVERSHEATH:
PVC according to French standard NF C 32-321 (PVC type ST2 according to International standard IEC 60502-1).
Core identification is according to standard EN 50334.
All cores in the cable are black and have an inscription along the whole length of them, except one core which is coloured green/yellow (this core isn´t numbered).
The inscription is composed of marks repeated at regular intervals along the whole length of the core.
Each mark comprises:
- A reference number beginning at 1 in Arabic numerals;
- A dash which underlines this number and indicates the direction in which the number should be read. -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
90ºC
-
Short-circuit temperature (5 s max):
250ºC
-
Voltage test:
3,5 kV AC (5 min)
-
Colour:
Black (Oversheath). EN 50334 (Black numbered cores + G/Y - Insulation).
-
Fire performance:
- Reaction to fire: Eca (EN 50575:2014+A1:2016)
• EN 60332-1-2; IEC 60332-1 (H≤425 mm) Flame retardant
For covered range (+ information), please check out "CPR/DoP" section in our website.
*The packaging labels of these cables include the CE marking according to the CPR Regulation ((EU) Nº 305/2011) articles 8 and 9. -
Type of installation:
Fixed
-
User´s guide:
BARRYNAX Múltiple U-1000 R2V is specially recommended for control installations in distribution networks, power stations, industries and buildings.
For indoor and outdoor installations. BARRYNAX Múltiple U-1000 R2V power cables are UV resistants (AN3) according to French standard NF C 32-321. -
Technical instructions:
.
-
Conductor:
Rigid
-
Halogen free:
No
-
Armoured cable:
No