Standards
EN 50525-2-21 / IEC 60245-4 / UNE 21150 (Construction and tests)
Low Voltage Directive: 2014/35/UE
CPR Regulation (UE) Nº 305/2011:
Reaction to fire (Eca)
IEC 60332-1-2 (Flame retardant)
RoHS compliant.
Quality certificate




Technical characteristics & performances
-
Single-core
-
Multicore
-
Flexible
-
Bunched conductor (class 5) mm2
-
Maximum service temperature: 90ºC / 250ºC
-
0,6/1 (1,2) kV C.A
-
Low temperature resistance
-
Easier pulling
-
Easy peeling / easy strip
Fire performance
-
Eca (reaction to fire)
-
Flame retardant
Uses and applications
-
Residential use
-
Industral use
-
Mobile service
-
Outdoor use
-
Indoor use
-
Provisional and temporary construction installations
-
Fairs and stands
-
Connection cable for machine tools
Packaging
-
Coil
-
Reel
-
Drum
Functional features
-
Technical designation:
DN-F / H07RN-F / H07RN8-F
-
Constructive description:
Single and multicore cable.
Conductor: Copper, flexible, class 5, acc. to IEC 60228.
Aislamiento: Crosslinked elastomer type EI 4 & EI7 (EN 50363-1) and type EPR (IEC 60502-1).
Cubierta exterior: Crosslinked elastomer type EM2 (EN 50363-2-1) and type SE1 (IEC 60502-1). Color: Black.
(*) Core identification: HD 308 S2:
2x: brown and blue
3x: brown, black and grey
3G: brown, blue and G/Y
4x: brown, black, grey and blue
4G: brown, black, grey and G/Y
5G: brown, black, grey, blue and G/Y.
6 or more: Black numbered + G/Y. -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
90 ºC
-
Short-circuit temperature (5 s max):
250 ºC (t<5s)
-
Voltage test:
3,5 kV AC. (5 minutes)
-
Colour:
Oversheath (black) / Insulations (HD 308 S2 / 6 or +: EN 50334).
-
Fire performance:
Reaction to fire: Eca
Flame retardant (IEC 60332-1-2). -
Type of installation:
Mobile
-
User´s guide:
For its use in industrial and agricultural workshops, building sites, for heavy duty applications and
supplying industrial and agricultural machines and appliances where cables are subject to medium
mechanical stresses (e.g. heating plates, inspection lamps, electric tools such as drills, circular
saws, and domestic electric tools). Suitable in dry, humid or moist rooms.
Fixed installations e.g. on rough-cast in temporary buildings and huts for accommodation purposes
In addition they are especially suitable for use as connection to machine tools.
Heavy duty applications. -
Conductor:
Flexible
-
Halogen free:
No
-
Armoured cable:
No