Standards
XP C32-325
(Construction & tests)
Fire retardant
(IEC 60332-1-2, IEC 60332-3-24, IEC 60754-1 & 2, & IEC 61034-2).
Low Voltage Directive: 2014/35/UE
Regulation CPR (EU) No 305/2011:
Reaction to fire (Cca-s1,d2,a1).
RoHS compliant
Quality certificate





Technical characteristics & performances
-
Single-core
-
Multicore
-
Solid conductor (class 1) mm2
-
Stranded conductor (class 2) mm2
-
Maximum service temperature: 90ºC / 250ºC
-
0,6/1 (1,2) kV C.A / 1,5 (1,8) kV C.C
-
UV resistance
-
Low temperature resistance
-
Presence of water
-
Easier pulling
-
Easy peeling / easy strip
Fire performance
-
Cca-s1,d2,a1
-
Fire retardant
-
Flame retardant
-
Low heat emission
-
Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
-
Halogen free
-
Low emission of toxic gases
-
Low smoke emission (s1)
Uses and applications
-
Distribution networks
-
Installations with risk of fire or explosion
-
BD2, BD3, BD4 (skyscrapers, tunnels…)
-
Buildings receiving the public
-
Residential use
-
Industral use
-
Exterior lighting
-
Outdoor use
-
Indoor use
-
IGH
-
Easy identification of the nominal cross-section of the conductors
Packaging
-
Coil
-
Reel
-
Drum
Functional features
-
Technical designation:
FR-N1X6G3-U (s = 1,5 / 2,5 / 4 mm2)
FR-N1X6G3-R (s≥ 6 mm2) -
Constructive description:
XP C32-325 (construction/tests)
- CONDUCTOR:
Annealed copper conductor, class 1 (s: 1,5, 2,5 or 4 mm2) or class 2 (from 6 mm2 up to 300 mm2) based on International standard IEC 60228.
- INSULATION:
Cross-linked polyolefin according to International standard IEC 60502-1.
- OVERSHEATH:
Thermoplastic polyolefin, halogen free (XP C32-325).
Oversheath color: Dark blue.
Available in single-core and multi-core configurations, with 1 to 5 cores.
1x(1,5-...-300) mm² / 2x(1,5-...-35) mm² / 3G(1,5-...-240) mm² / 4x(1,5-...-185) mm² / 5G(1,5-...-25) mm².
The black oversheath of the multicore cablas (2, 3, 4, 5)Xo G(1,5-...-16mm2) should have a coloured stripe to indicate the nominal cross-sectional area of copper conductors.
Cross sectional area mm2 Color code
1,5 Pink
2,5 Yellow
4 Violet
6 Turqoise
10 Brown
16 Gray
Identification of cores (HD 308 S2 / UNE 21089-1):
2x - brown and blue
3x - brown, black and blue (S=1,5/2,5 mm2)
3x - brown, black and gray (S≥4 mm2)
3G - brown, blue and yellow / green
4x - brown, black, gray and blue
4G - brown, black, gray and yellow / green
5G - brown, black, gray, blue and yellow / green -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
90ºC
-
Short-circuit temperature (5 s max):
250ºC (t<5s)
-
Voltage test:
3,5 kV (5 min.)
-
Colour:
Sheath: Dark blue / Insulation (multicore): According to HD 308 S2, UNE 21089-1
-
Fire performance:
REACTION TO FIRE:
- Reaction to fire (Regulation CPR (EU) Nº 305/2011).
Cca-s1,d2,a1.
- Fire retardant, halogen free:
IEC 60332-1-2, IEC 60332-3-24, IEC 60754-1 & 2, & IEC 61034-2. -
Type of installation:
Fixed
-
User´s guide:
Fixed installation.
FR-N1X6G3 power cables are specially indicated for its use in distribution networks, power stations, industries or buildings.
They are designed to limit the risk of fire spread, minimize the smokes emitted in the event of a fire, and reduce the corrosiveness and toxicity of gases released during combustion. This advanced performance helps protect both people and property from the devastating secondary effects of a fire.
The use of these cables is especially recommended for BD2, BD3, or BD4 installations (HD 60364-5-51), particularly due to their low emission of gases and smoke with low toxicity, corrosiveness, acidity and opacity.
Suitable for indoor and outdoor installations, on supports in the air, in conduits or buried (protected). -
Technical instructions:
.
-
Conductor:
Rigid
-
Halogen free:
Yes
-
Armoured cable:
No