Standards
IEC 60502-1 y UNE 21123-4 (Standards (construction/tests)).
LOW VOLTAGE DIRECTIVE: 2014/35/EU
CPR Regulation (EU) No 305/2011:
Reaction to fire (Cca-s1b,d1,a1)
Additional fire performance features
(when CPR Regulation is not applicable):
IEC 60332-1-2, IEC 60332-3-24, IEC 61034-2, IEC 60754-1, IEC 60684-2 e IEC 60754-2.
RoHS compliant
Quality certificate




Technical characteristics & performances
-
Single-core
-
Stranded conductor (class 2) mm2
-
Maximum service temperature: 90ºC / 250ºC
-
0,6/1 (1,2) kV C.A / 1,5 (1,8) kV C.C
-
Low temperature resistance
Fire performance
-
Cca-s1b,d1,a1 (reaction to fire)
-
Fire retardant
-
Flame retardant
-
Low heat emission
-
Low production of flaming droplets
-
Low opacity & production of smoke
-
Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
-
Halogen free
-
Low emission of toxic gases
-
Low smoke emission (s1)
Uses and applications
-
Distribution networks
-
Installations with risk of fire or explosion
-
BD2, BD3, BD4 (skyscrapers, tunnels…)
-
Buildings receiving the public
-
Industral use
-
Exterior lighting
-
Outdoor use
Packaging
-
Drum
DOWNLOADS:
Technical DatasheetFunctional features
-
Technical designation:
RZ1 (AS) 0,6/1 kV Al
-
Constructive description:
CONSTRUCTION:
- Conductor: Aluminium, class 2, circular compacted stranded conductor (IEC 60228).
- Insulation: Cross-linked polyethylene (XLPE). XLPE (IEC 60502-1) & type DIX 3 (HD 603-1 table 2).
- Oversheath: Halogen-free thermoplastic polyolefin. Type ST8 (IEC 60502-1) & type DMZ-E (UNE 21123-4).
Range: Single-core cable.
Configurations: 1X(25-...-630) mm².
- Metric markings on the oversheath every 1.0 m.
- Inclusion of manufacturing order number for total traceability.
Rated Voltage (Uo/U): 0.6/1 kV AC; 1.5 kV DC.
Maximum allowable voltage (Um): 1.2 kV AC; 1.8 kV DC. -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
90ºC
-
Short-circuit temperature (5 s max):
250ºC (t<5s)
-
Voltage test:
3,5 kV CA (5 minutes)
-
Colour:
Oversheath colour: Green
-
Fire performance:
Reaction to fire (CPR - EN 50575 & EN 13501-6): Cca-s1b,d1,a1.
Additional fire performance features (when CPR Regulation is not applicable):
Flame retardant, fire retardant, halogen-free and low gas and smoke emission with low opacity/toxicity/corrosivity/conductivity
(IEC 60332-3-24, IEC 60332-1-2, IEC 60754-1, IEC 60754-2 and IEC 61034-2). -
Type of installation:
Fixed
-
User´s guide:
Fixed installations. Specially suitable as power cable in public buildings, premises with risk of fire or explosion, high-rise buildings, tunnels, and any other installation requiring enhanced fire performance (e.g. cable bunches, vertical risers, etc.).
Suitable for indoor and outdoor installations, on support in open air, in ducts or buried.
Temperature ranges:
- Minimum ambient temperature: - 30 °C (fixed, static installation, protected against mechanical damage, shock, or vibration).
- Maximum ambient temperature: + 70 °C.
- Maximum storage temperature: + 50 °C.
- Minimum laying temperature: 0 °C.
Minimum Bending Radius:
During installation: 15×D.
Final position: 10×D.
D = overall diameter of the cable (mm).
Maximum pulling force during Installation:
F = 30×S (N). "S" = cross-sectional area of the conductor (mm²), applied to conductors.
F = 5×D² (N). "D" = overall diameter (mm), applied to oversheath. -
Conductor:
Rigid
-
Halogen free:
Yes
-
Armoured cable:
No