Standards
IEC 60502-1 (Construcción y ensayos)
IEC 60332-1-2, IEC 60332-24, IEC 60754-1 y 2, IEC 61034-2
(Comportamiento en caso de incendio)
LOW VOLTAGE DIRECTIVE: 2014/35 / EU
RoHS compliant
Quality certificate
Technical characteristics & performances
- Single-core
- Multicore
- Bunched conductor (class 5) mm2
- Maximum service temperature: 90ºC / 250ºC
- 0,6/1 (1,2) kV C.A
- Mechanical protection
- Oil resistance
- Low temperature resistance
- Anti rodents
Fire performance
- Flame retardant
- Fire retardant
- Low opacity & production of smoke
- Low acidity & conductivity of the gases: pH<4,3 10 µS/mm
- Halogen free
- Low emission of toxic gases
Uses and applications
- Distribution networks
- Installations with risk of fire or explosion
- BD2, BD3, BD4 (skyscrapers, tunnels…)
- Buildings receiving the public
- Industral use
- Exterior lighting
- Outdoor use
Packaging
- Drum
DOWNLOADS:
Technical DatasheetFunctional features
-
Technical designation:
RZ1FAZ1-K(AS) 0,6/1 kV (single core cables) / RZ1FZ1-K(AS) 0,6/1 kV (multicore cables)
-
Constructive description:
IEC 60502-1, UNE 21123-4 (Construction and tests)
- CONDUCTOR:
Flexible, annealed, plain copper conductor, class 5 based on standard IEC 60228.
- INSULATION:
Cross-linked polyethylene (XLPE) according to International standard IEC 60502-1
- ASSEMBLY OF CONDUCTORS:
In multicore cables, the cores are cabled helically.
- INNER SHEATH:
Extruded polyolefin type ST8 according to International standard IEC 60502-1.
- ARMOUR:
Steel (multicore cables) or aluminium (single-core cables) double tape armour.
The armour is in accordance with International standard IEC 60502-1.
- OVERSHEATH:
Extruded polyolefin type ST8 according to International standard IEC 60502-1.
Identification of cores HD 308 S2:
2x - brown and blue
3x - brown, black and gray
3G - brown, blue and yellow / green
4x - brown, black, gray, blue
4G - brown, black, gray, yellow / green
5G - brown, black, gray, blue, yellow / green -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
90ºC
-
Short-circuit temperature (5 s max):
250ºC
-
Voltage test:
3,5 kV
-
Colour:
Green
-
Fire performance:
- Flame retardant: UNE EN 60332-1-2 ; IEC 60332-1-2 (H≤425 mm)
- Fire retardant: UNE EN 60332-3-24 / IEC 60332-3-24 (cat.C) (H ≤ 2,5 m)
- Low opacity of emitted smokes: UNE EN 61034-2; IEC 61034-2
60% < Light transmittance. In case of fire, it avoids loss of visibility due to smoke produced by cable combustion
- Low acidity and conductivity of the emitted gases: EN 60754-2; IEC 60754-2
pH≥4,3 conductivity < 10 microsiemens/mm
- Halogen free. Low emission of toxic gases: UNE EN 50267-2-1 / IEC 60754-1 (HCl <0,5 % y Fluor < 0,1 %) -
Type of installation:
Fixed
-
User´s guide:
It is specially indicated for its use in distribution networks, public concurrence places (airports, museums, malls, schools, hospitals, cinemas,...) and in general, whenever an important fire risk exists or where it´s required a low smoke emission and corrosive gases in case of fire.
Its use is recommended for installations with presence of rodents, and installations in general where the cable is subject to risk of mechanical aggresion.
Its special fire performance protects public health, fireman works and avoid any possible damage to electronic equipments. -
Technical instructions:
.
-
Conductor:
Flexible
-
Halogen free:
Yes
-
Armoured cable:
Yes