Standards
UNE-HD 603-5X (Standards (construction/tests)).
LOW VOLTAGE DIRECTIVE: 2014/35/EU
CPR Regulation (EU) No 305/2011:
Reaction to fire (Eca)
Additional fire performance features
(when CPR Regulation is not applicable):
IEC 60332-1-2, IEC 60754-1, IEC 60754-2 & IEC 61034-2.
RoHS compliant
Quality certificate





Technical characteristics & performances
-
Single-core
-
Stranded conductor (class 2) mm2
-
Maximum service temperature: 90ºC / 250ºC
-
0,6/1 (1,2) kV C.A / 1,5 (1,8) kV C.C
-
Mechanical protection
-
UV resistance
-
Low temperature resistance
-
Presence of water
-
Easier pulling
Fire performance
-
Eca (reaction to fire)
-
Flame retardant
-
Low opacity & production of smoke
-
Low acidity & conductivity of the gases: pH<4,3 10 µS/mm
-
Halogen free
-
Low emission of toxic gases
Uses and applications
-
PV installations
-
Distribution networks
-
Industral use
-
Exterior lighting
-
Outdoor use
-
Indoor use
Packaging
-
Drum
Functional features
-
Technical designation:
XZ1 (S) 0.6/1 kV Al
-
Constructive description:
- Conductor: Aluminium, class 2, circular compacted stranded conductor (IEC 60228).
- Insulation: Cross-linked polyethylene (XLPE). XLPE (IEC 60502-1) & type DIX 3 (HD 603-1).
- Oversheath: Halogen-free thermoplastic polyolefin. Type DMO 1 (HD 603-1).
Rated Voltage (Uo/U): 0.6/1 kV AC; 1.5 kV DC.
Maximum allowable voltage (Um): 1.2 kV AC; 1.8 kV DC.
Suitable for low-voltage category B networks according to IEC 60183 (UNE-HD 603-1).
Range: Single-core cable.
Configurations: 1X(16-...-630) mm².
- Metric markings on the oversheath every 1.0 m.
- 100% recyclable packaging. Wooden reels (PEFC and SFC certified).
- Inclusion of manufacturing order number for total traceability.
Packaging and Presentation:
- Drum/cut to length.
- Minimum free space on drum flanges: 5 cm.
- Minimum core diameter of the drum: 12×D (D = cable outer diameter).
- Manual coils: Minimum core diameter: 15×D. (D = cable outer diameter). -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
90 ºC
-
Short-circuit temperature (5 s max):
250 ºC (t < 5 s)
-
Voltage test:
6.5 kV AC (5 minutes)
1.8 kV AC (4 hours)
10 kV AC (30 minutes)
Impulse Voltage Test (1.2/50 µs): 20 kV. -
Colour:
Insulation color: No coloration / Oversheath color: Black.
-
Fire performance:
Reaction to fire (CPR - EN 50575 & EN 13501-6): Eca.
Additional fire performance features (when CPR Regulation is not applicable):
Flame retardant, halogen-free and low gas and smoke emission with low opacity/toxicity/corrosivity/conductivity
(IEC 60332-1-2, IEC 60754-1, IEC 60754-2 and IEC 61034-2). -
Type of installation:
Fixed
-
User´s guide:
Halogen-free power cable, especially suitable for fixed installations in low-voltage distribution networks, buried or underground service connections, photovoltaic systems and industrial installations. Suitable for indoor and outdoor installations, on supports in the air, in conduits or buried.
Weather and UV resistant: Condition AN3 (HD 60364-5-51).
Suitable for installation under condition AD7 (HD 60364-5-51).
Abrasion Resistance: High resistance thanks to its special oversheath.
The adherence between insulation and sheath ensures a high sealing index.
Temperature ranges:
- Minimum ambient temperature: - 30 °C (fixed, static installation, protected against mechanical damage, shock, or vibration).
- Maximum ambient temperature: + 70 °C.
- Maximum storage temperature: + 50 °C.
- Minimum laying temperature: 0 °C.
Minimum Bending Radius:
During installation: 15×D.
Final position: 10×D.
D = overall diameter of the cable (mm).
Maximum pulling force during Installation:
F = 30×S (N). "S" = cross-sectional area of the conductor (mm²), applied to conductors.
F = 5×D² (N). "D" = overall diameter (mm), applied to oversheath. -
Technical instructions:
.
-
Conductor:
Rigid
-
Halogen free:
Yes
-
Armoured cable:
No