Standards
IEC 60502-1, UNE 21123-2
(Construction and tests)
LOW VOLTAGE DIRECTIVE: 2014/35/EU
Regulation CPR (EU) No 305/2011:
Reaction to fire (Eca)
RoHS compliant
Quality certificate
Technical characteristics & performances
- Single-core
- Multicore
- Solid conductor (class 1) mm2
- Stranded conductor (class 2) mm2
- Maximum service temperature: 90ºC / 250ºC
- 0,6/1 (1,2) kV C.A
- Mechanical protection
- Low temperature resistance
- Anti rodents
Fire performance
- Eca (reaction to fire)
- Flame retardant
Uses and applications
- Distribution networks
- Industral use
- Exterior lighting
- Outdoor use
Packaging
- Drum
DOWNLOADS:
Technical DatasheetFunctional features
-
Technical designation:
RVFAV 0,6/1 kV : Single-core cables RVFV 0,6/1 kV: Multicore cables.
-
Constructive description:
IEC 60502-1, UNE 21123-2 (Construction and tests)
- CONDUCTOR:
Annealed copper conductor, class 1(s: 1,5/2,4 or 4 mm2) or class 2 (from 6 mm2 up to 300 mm2) based on International standard IEC 60228 / EN 60228.
- INSULATION:
Cross-linked polyethylene (XLPE) according to International standard IEC 60502-1
- ASSEMBLY OF CONDUCTORS:
In multicore cables, the cores are cabled helically.
- INNER SHEATH:
PVC type ST2 according to International standard IEC 60502-1.
- ARMOUR:
Steel (multicore cables) or aluminium (single-core cables) double tape armour.
The armour is in accordance with UNE 21123-2 / IEC 60502-1.
- OUTER SHEATH:
PVC type ST2 according to International standard IEC 60502-1.
Identification of cores HD 308 S2:
2x - brown and blue
3x - brown, black and gray
3G - brown, blue and yellow / green
4x - brown, black, gray, blue
4G - brown, black, gray, yellow / green
5G - brown, black, gray, blue, yellow / green -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
90ºC
-
Short-circuit temperature (5 s max):
250ºC
-
Voltage test:
3,5 kV
-
Colour:
Black
-
Fire performance:
- Reaction to fire: Eca (EN 50575:2014+A1:2016)
• EN 60332-1-2; IEC 60332-1 (H≤425 mm) Flame retardant
For covered range (+ information), please check out "CPR/DoP" section in our website.
*The packaging labels of these cables include the CE marking according to the CPR Regulation ((EU) Nº 305/2011) articles 8 and 9. -
Type of installation:
Fixed
-
User´s guide:
It is specially indicated for its use in distribution networks in which there is a high risk of mechanical aggressions or tensile stress.
Its use is recommended for installations with presence of rodents and installations in general where the cable is subject to risk of mechanical aggression. -
Technical instructions:
.
-
Conductor:
Rigid
-
Halogen free:
No
-
Armoured cable:
Yes